Data Sheet 705000 Page 5/10
JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany
Phone: +49 661 6003-0
Fax: +49 661 6003-607
Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax: +44 1279 635262
Internet: www.jumo.co.uk
JUMO Process Control, Inc.
6733 Myers Road
East Syracuse, NY 13057, USA
Phone: 315-437-5866
1-800-554-5866
Fax: 315-437-5860
Internet: www.jumousa.com
Input/output modules
The modules are equipped with removable terminal strips with Push-In technology for the electrical connection.
All input/output modules operate at a voltage supply of DC 24 V.
The setup program, the multifunction panel or the optional PLC can be used to comfortably configure and parameterize the modules.
LEDs are used to indicate the voltage supply as well as the operating status of a module and the input/output statuses.
For service work (replacement) or adding optional boards, the module insert can be easily pulled out of the case at the front.
Multichannel controller module
Relay module 4-channel
2-channel PID controller with relay output or logic output
to control solid-state relays
Up to 4 PID controller channels can be activated (cascadable)
Two universal analog inputs, two digital inputs
(DC 0/24 V) and two digital outputs (relay or logic DC 0/15 V)
Supported measuring probes: Thermocouples, RTD temperature
probes, resistance transmitters, resistance/potentiometers, or
standard signals (current or voltage)
The analog inputs are electrically isolated from each other
Three option slots for the extension of up to four
universal analog inputs, eight digital inputs,
three analog outputs, or eight digital outputs
Supported controller types: Two-state controller, three-state con-
troller, modulating controller, continuous controller, or continuous
controller with integrated actuator controller
Customer-specific linearization possible by using a formula
Limit value monitoring
Four formulae for math and logic functions (option)
One counting input up to 10 kHz
The module operates independently (configurable) which means
the control task is carried out even if the base unit or the higher-
ranking system malfunctions
If the controller is replaced during service work the new controller
(identical type) is automatically configured
Dimensions (W x H x D): 45 mm x 103.6 mm x 101.5 mm
(without connection elements)
For further information: Refer to data sheet 705010
Four relay outputs controlled via the system bus by digital signals
Each relay is equipped with a changeover contact
AC 230 V / 3 A
Separate terminal strip per relay output
Automatic configuration after the module insert has been ex-
changed during service work
Dimensions (W x H x D): 22.5 mm x 103.6 mm x 101.5 mm
(without connection elements)
For further information: Refer to data sheet 705015